- Full Catalog
- Tripp Lite
- Systems
- UPS & Power Devices
-
Tripp Lite SmartOnline 208/240V 6kVA On-Line UPS
- Back to Results
Main Specifications
|
---|
Product Description
|
Tripp Lite SmartOnline 208/240V 6kVA On-Line UPS - Double Conversion, 5.4kW, 4U, Network Card Option, TAA Compliant - UPS - 5.4 kW - 6000 VA - TAA Compliant
|
Device Type
|
UPS - rack-mountable
|
Rack Size
|
19" - 4U
|
Weight
|
108 lbs
|
Input Wiring
|
1-phase
|
Input Voltage
|
AC 200/208/240 V
|
Output Voltage
|
AC 200/208/240 V ± 2%
|
Power Capacity
|
5.4 kW / 6000 VA
|
Input Connectors
|
1 x power NEMA L6-30P
|
Output connectors
|
2 x power NEMA L6-20R (UPS and surge) ¦ 2 x power NEMA L6-30R (UPS and surge)
|
Battery
|
Expandable
|
Run Time (Up To)
|
2 min at full load
|
Networking
|
RS-232, USB
|
TAA Compliant
|
TAA Compliant
|
Dimensions (WxDxH)
|
17.5 in x 20.7 in x 6.9 in
|
Manufacturer Warranty
|
2-year warranty
|
General
|
---|
Device Type
|
UPS - rack-mountable
|
Height (Rack Units)
|
4U
|
Rack Size
|
19"
|
Expansion / Connectivity
|
---|
Interfaces
|
1 x USB - 4 pin USB Type B ¦ 1 x RS-232 - 9 pin D-Sub (DB-9)
|
Expansion Slots
|
1 (total) / 1 (free) x expansion slot
|
Manufacturer Warranty
|
---|
Service & Support
|
Limited warranty - 2 years
|
Miscellaneous
|
---|
Cables Included
|
Power cable - external - 10 ft ¦ USB cable - external ¦ Serial cable - external
|
Rack Mounting Kit
|
Included
|
Features
|
Audible alarm, LCD display, noise filtering, cold-start function
|
Compliant Standards
|
CSA, UL 1778, RoHS, EMI, FCC CFR47 Part 15 A, IEC 61000-4-5:1995
|
TAA Compliant
|
Yes
|
Networking
|
---|
Remote Management Interface
|
RS-232, USB
|
Software / System Requirements
|
---|
Software Included
|
TrippLite PowerAlert
|
Environmental Parameters
|
---|
Min Operating Temperature
|
32 °F
|
Max Operating Temperature
|
104 °F
|
Humidity Range Operating
|
0 - 95% (non-condensing)
|
Sound Emission
|
60 dBA
|
Battery
|
---|
Type
|
Expandable
|
Voltage Provided
|
192 V
|
Run Time (Up To)
|
2 min at full load ¦ 8.5 min at half load
|
Recharge Time
|
6 hours
|
Power Device
|
---|
UPS Technology
|
On-line
|
Input Voltage
|
AC 200/208/240 V
|
Frequency Provided
|
50/60 Hz
|
Input Wiring
|
1-phase
|
Frequency Required
|
50/60 Hz
|
Input Connectors
|
1 x power NEMA L6-30P
|
Power Output Connectors Details
|
2 x power NEMA L6-20R (UPS and surge) ¦ 2 x power NEMA L6-30R (UPS and surge)
|
Output Voltage
|
AC 200/208/240 V ± 2% - 50/60 Hz
|
Power Capacity
|
5.4 kW / 6000 VA
|
Output Waveform
|
Sinewave
|
Surge Suppression
|
Yes
|
Circuit Protection
|
Circuit breaker
|
Efficiency
|
90% at 100% Load, 96% at 100% Load Eco mode
|
Power Factor (PF)
|
0.9
|
Dimensions & Weight
|
---|
Width
|
17.5 in
|
Depth
|
20.7 in
|
Height
|
6.9 in
|
Weight
|
108 lbs
|
Dimensions & Weight (Shipping)
|
---|
Shipping Width
|
36 in
|
Shipping Depth
|
24 in
|
Shipping Height
|
30 in
|
Shipping Weight
|
189.99 lbs
|